H7CN-XHNS AC100-240 Controlador Digital H7CN-XHNS-AC100-240, 4 digitos Omron

DESCRIPCIÓN

Controlador Digital H7CN-XHNS-AC100-240, 4 digitos Omron 

Function Preset Counter
Preset stages 1stages
Rated supply voltage 100 to 240 VAC 50/60 Hz
Operating voltage range 85% to 110% of the rated power supply voltage
Power consumption Approx. 12 VA (at 100 VAC)
Counter (Count range) 0~9999
Counter (Max. counting speed) 5 kHz (Minimum counting input signal width: 0.1 ms (ON/OFF ratio: 1:1))
Counter (Input mode) Increment
Counter (Output modes) N
Counter (Reset system) External, manual and power reset
Input signal Count / Reset / CP1 / CP2
Input method No-voltage input
No-voltage input (No-contact input) Short-circuit (ON) impedance: 1 kΩ
Residual voltage: 2 V max.
Open circuit impedance: 100 kΩ
No-voltage input (Contact input) Use a contact which can adequately switch 0.5 mA at 5 V.
Minimum input signal width External reset: 20 ms
Manual reset: 20 ms
Power reset: 500 ms
Control output (Contact output) -
Control output (Solid-state output) Output type: Transistor output (NPN open collector)
Switching capacity: 30 VDC max., 100 mA max.
Display method 7-segment LED
Digits 4digits
Character height Count value: 10 mm (Red)
Zero suppression: Not provided
Prescaling function Not provided
Key protection Not provided
Teaching function Not provided
Batch counting function Not provided
Communications Not provided
Memory backup Not provided ()
Surrounding air temperature Operating: -10 to 55 ℃
Storage: -25 to 65 ℃
Ambient humidity Operating: 35 to 85%
Storage: 35 to 85%
Insulation resistance 100 MΩ min. (at 500 VDC)
Between current carrying terminals and exposed non-current carrying metal parts / Between control output terminals and operating circuit
Dielectric withstand voltage Between current carrying terminals and exposed non-current carrying metal parts:2000 VAC 50/60 Hz for 1 min
Between control output terminals and operating circuit:2000 VAC 50/60 Hz for 1 min
Impulse withstand voltage Between power terminals:6.0 kV
Between current carrying terminals and exposed non-current carrying metal parts:6.0 kV
Noise immunity Between power terminals:±2k V
Between input terminals:±500 V
Square-wave noise by noise simulator (Pulse width: 100 ns/1 µs, 1-ns rise)
Static immunity ±8 kV (malfunction)
Vibration resistance (Destruction) 10 to 55 Hz, 0.75-mm single amplitude each in 3 directions for 2 h
Vibration resistance (Malfunction) 10 to 55 Hz, 0.5-mm single amplitude each in 3 directions for 10 min
Shock resistance (Destruction) 300 m/s**2, 3 times each in 6 directions (3 axes)
Shock resistance (Malfunction) 100 m/s**2, 3 times in each directions (3 axes)
Degree of protection Case front: IP40
Case rear: IP40
Terminal block: IP00
Mounting method Flush mounting/Surface mounting
External connection method 8-pinSocket
Case color Light gray (Munsell 5Y7/1)
Weight Approx. 110 g
 

 

 


FICHA TECNICA